Cable sizing

Cable Sizing Calculator

IEC 60364-5-52 cable sizing with the ampacity + voltage-drop dual constraint, ambient and grouping derating, and regional defaults for KSA, UAE, Egypt, and the IEC baseline.

Selected cable size
4 mm²
Cu / XLPE — 3-phase
Voltage drop
3.44%
13.8 V vs 5.0% limit
Design current
32.1 A
20 kW @ 400 V × PF 0.9
Derating Ca × Cg
100%
Ca 1.00 (30 °C) × Cg 1.00 (1 circuit)
Derated ampacity
42 A
Base 42 A × derating

Why this size, not the next one down

4 mm² is the smallest standard size where derated ampacity (42 A) exceeds the design current (32.1 A) AND voltage drop (3.44%) stays within the 5.0% limit. Both constraints must pass — the smaller of the two is what bites. Reactance is ignored — the cable is small enough that resistance dominates the voltage drop.

Cable sizing per UPS, automatic and saved.

Power Stack stores the cable spec for every UPS you've installed — input length, load, ambient, and re-sizes the moment customer load grows. No more rebuilding the calculation from scratch on every quote.

Start free

The two constraints that decide cable size

Cable sizing per IEC 60364-5-52 is a dual-constraint problem. The cable must be large enough to carry the design current without overheating its insulation, AND it must be large enough that the voltage drop across its length stays within the regulated maximum. Most spreadsheet calculators handle one or the other. Picking the larger of the two is the only correct answer — and which one bites depends on the run length, the power factor, and how aggressively the site has been derated.

Ampacity, then derated ampacity

The IEC 60364-5-52 Method C table lists base ampacity for each standard mm² size, copper, single-core, clipped direct, in still air at 30 °C. Two corrections derate that base figure: Ca for ambient temperature (sub-30 °C boosts ampacity, hot sites cut it sharply — at 50 °C, PVC is at 71% of its 30 °C rating), and Cg for grouping (touching cables in the same conduit derate each other — 3 circuits cut ampacity to 70%, 6 circuits to 57%). The required ampacity from the table is the design current divided by (Ca × Cg). For aluminium, multiply the copper ampacity by 0.78.

Voltage drop: the second constraint

Voltage drop scales linearly with cable length and current, and inversely with cross-section. For cables under 25 mm², resistance dominates and the simplified formula Vd = k × ρ × L × I × cos φ / S gives the right answer. Above 25 mm² (and above 16 mm² when power factor drops below 0.9), reactance becomes a meaningful share of the total and the formula expands to include the X sin φ term. National codes set the limits: 5% from origin to load is the IEC baseline, 2.5% for DEWA final circuits, 3% is common practice for sub-mains and feeders.

Why the regional defaults matter

Indoor ambient in a chilled office in northern Europe is 20–25 °C; outdoor in summer in the Gulf is 45–50 °C. Sizing the same load for both sites gives different answers — and a cable that's ampacity-correct in a temperate site can be one or two size steps short when installed in a hot region. The region defaults in this calculator preset Ca and the voltage- drop limit to the typical values for KSA, UAE, and Egypt, and fall back to a generic IEC baseline (30 °C ambient, 5% drop limit) for everywhere else. Override the defaults whenever your site differs.

Standards behind the math

Ampacity values from IEC 60364-5-52 Ed. 3.1 (2024-11) Method C, copper, single-core in air. Aluminium ampacity is the IEC convention of 0.78 × copper. Ca tables from IEC 60364-5-52 Table B.52.14; Cg from Table B.52.17 (touching, single layer). Resistivity from IEC 60228 with the standard temperature coefficient applied at the insulation rating (70 °C PVC, 90 °C XLPE). Reactance simplified to 0.08 mΩ/m, the Schneider EIG cross-vendor value for typical LV cable.

Cable sizing — important limitations: This calculator checks ampacity (IEC 60364-5-52) and voltage drop only. It does NOT verify short-circuit withstand, earth-fault loop impedance, protective-device coordination, neutral sizing for harmonic loads, or compliance with your local wiring code. Single-core vs multicore, tray spacing, buried-soil thermal resistivity, solar exposure, and the upstream protective device are all out of scope. Use this output as a starting point only; final cable specification must be verified by a qualified electrical engineer and reconciled with manufacturer datasheets, the applicable national wiring regulations (NEC, BS 7671, IEC 60364, or your local equivalent), and site-specific conditions. Power Stack accepts no liability for installation decisions made from this output.